Data Code |
Short Description |
Long Description |
Address Field |
|
CJ |
Late Close |
An area was armed after the closing window |
User number |
|
CK |
Early Close |
An area was armed before the closing window |
User number |
|
CL |
Closing Report |
System armed, normal |
User number |
|
CM |
Missing Alarm - Recent Closing |
A point has gone missing within 2 minutes of closing |
Zone or point |
|
CO |
Command Sent |
A command has been sent to an expansion/peripheral device |
Condition number |
|
CP |
Automatic Closing |
System armed automatically |
User number |
|
CQ |
Remote Closing |
The system was armed from a remote location |
User number |
|
CR |
Recent Closing |
An alarm occurred within five minutes after the system was closed |
User number |
|
CS |
Closing Keyswitch |
Account has been armed by keyswitch |
Zone or point |
|
CT |
Late to Open |
System was not disarmed on time |
Area number |
|
CW |
Was Force Armed |
Header for a force armed session, forced point msgs may follow |
Area number |
|
CX |
Custom Function Executed |
The panel has executed a preprogrammed set of instructions |
Custom Function number |
|
CZ |
Point Closing |
A point, as opposed to a whole area or account, has closed |
Zone or point |
|
DA |
Card Assigned |
An access ID has been added to the controller |
User number |
|
DB |
Card Deleted |
An access ID has been deleted from the controller |
User number |
|
DC |
Access Closed |
Access to all users prohibited |
Door number |
|
DD |
Access Denied |
Access denied, unknown code |
Door number |
|
DE |
Request to Enter |
An access point was opened via a Request to Enter device |
Door number |
|
DF |
Door Forced |
Door opened without access request |
Door number |
|
DG |
Access Granted |
Door access granted |
Door number |
|
DH |
Door Left Open - Restoral |
An access point in a Door Left Open state has restored |
Door number |
|
DI |
Access Denied – Passback |
Access denied because credential has not exited area before attempting to re-enter same area |
Door number |
|
DJ |
Door Forced - Trouble |
An access point has been forced open in an unarmed area |
Door number |
|
DK |
Access Lockout |
Access denied, known code |
Door number |
|
DL |
Door Left Open - Alarm |
An open access point when open time expired in an armed area |
Door number |
|
DM |
Door Left Open - Trouble |
An open access point when open time expired in an unarmed area |
Door number |
|
DN |
Door Left Open (non-alarm, non-trouble) |
An access point was open when the door cycle time expired |
Door number |
|
DO |
Access Open |
Access to authorized users allowed |
Door number |
|
DP |
Access Denied - Unauthorized Time |
An access request was denied because the request is occurring outside the user’s authorized time window(s) |
Door number |
|
DQ |
Access Denied Unauthorized Arming State |
An access request was denied because the user was not authorized in this area when the area was armed |
Door number |
|
DR |
Door Restoral |
Access alarm/trouble condition eliminated |
Door number |
|
DS |
Door Station |
Identifies door for next report |
Door number |
|
Data Code |
Short Description |
Long Description |
Address Field |
|
DT |
Access Trouble |
Access system trouble |
Unused |
|
DU |
Dealer ID |
Dealer ID number |
Dealer ID |
|
DV |
Access Denied Unauthorized Entry Level |
An access request was denied because the user is not authorized in this area |
Door number |
|
DW |
Access Denied - Interlock |
An access request was denied because the doors associated Interlock point is open |
Door number |
|
DX |
Request to Exit |
An access point was opened via a Request to Exit device |
Door number |
|
DY |
Door Locked |
The door’s lock has been engaged |
Door number |
|
DZ |
Access Denied - Door Secured |
An access request was denied because the door has been placed in an Access Closed state |
Door number |
|
EA |
Exit Alarm |
An exit zone remained violated at the end of the exit delay period |
Zone or point |
|
EE |
Exit Error |
An exit zone remained violated at the end of the exit delay period |
User number |
|
EJ |
Expansion Tamper Restore |
Expansion device tamper restoral |
Expansion device number |
|
EM |
Expansion Device Missing |
Expansion device missing |
Expansion device number |
|
EN |
Expansion Missing Restore |
Expansion device communications re-established |
Expansion device number |
|
ER |
Expansion Restoral |
Expansion device trouble eliminated |
Expander number |
|
ES |
Expansion Device Tamper |
Expansion device enclosure tamper |
Expansion device number |
|
ET |
Expansion Trouble |
Expansion device trouble |
Expander number |
|
EX |
External Device Condition |
A specific reportable condition is detected on an external device |
Device number |
|
EZ |
Missing Alarm - Exit Error |
A point remained missing at the end of the exit delay period |
Point number |
|
FA |
Fire Alarm |
Fire condition detected |
Zone or point |
|
FB |
Fire Bypass |
Zone has been bypassed |
Zone or point |
|
FC |
Fire Cancel |
A Fire Alarm has been cancelled by an authorized person |
Zone or point |
|
FG |
Unverified Event – Fire |
A point assigned to a Cross Point group has gone into alarm but the Cross Point remained normal |
Zone or point |
|
FH |
Fire Alarm Restore |
Alarm condition eliminated |
Zone or point |
|
FI |
Fire Test Begin |
The transmitter area's fire test has begun |
Area number |
|
FJ |
Fire Trouble Restore |
Trouble condition eliminated |
Zone or point |
|
FK |
Fire Test End |
The transmitter area's fire test has ended |
Area number |
|
FL |
Fire Alarm Silenced |
The fire panel’s sounder was silenced by command |
Zone or point |
|
FM |
Fire Alarm - Cross Point |
Fire Alarm with Cross Point also in alarm verifying the Fire Alarm |
Point number |
|
FQ |
Fire Supervisory Trouble Restore |
A fire supervisory zone that was in trouble condition has now restored to normal |
Zone or point |
|
FR |
Fire Restoral |
Alarm/trouble condition has been eliminated |
Zone or point |
|
Data Code |
Short Description |
Long Description |
Address Field |
|
FS |
Fire Supervisory |
Unsafe fire detection system condition |
Zone or point |
|
FT |
Fire Trouble |
Zone disabled by fault |
Zone or point |
|
FU |
Fire Unbypass |
Bypass has been removed |
Zone or point |
|
FV |
Fire Supervision Restore |
A fire supervision zone that was in alarm has restored to normal |
Zone or point |
|
FW |
Fire Supervisory Trouble |
A fire supervisory zone is now in a trouble condition |
Zone or point |
|
FX |
Fire Test |
Fire zone activated during test |
Zone or point |
|
FY |
Missing Fire Trouble |
A fire point is now logically missing |
Zone or point |
|
FZ |
Missing Fire Supervision |
A Fire Supervisory point has gone missing |
Zone or point |
|
GA |
Gas Alarm |
Gas alarm condition detected |
Zone or point |
|
GB |
Gas Bypass |
Zone has been bypassed |
Zone or point |
|
GH |
Gas Alarm Restore |
Alarm condition eliminated |
Zone or point |
|
GJ |
Gas Trouble Restore |
Trouble condition eliminated |
Zone or point |
|
GR |
Gas Restoral |
Alarm/trouble condition has been eliminated |
Zone or point |
|
GS |
Gas Supervisory |
Unsafe gas detection system condition |
Zone or point |
|
GT |
Gas Trouble |
Zone disabled by fault |
Zone or point |
|
GU |
Gas Unbypass |
Bypass has been removed |
Zone or point |
|
GX |
Gas Test |
Zone activated during test |
Zone or point |
|
HA |
Holdup Alarm |
Silent alarm, user under duress |
Zone or point |
|
HB |
Holdup Bypass |
Zone has been bypassed |
Zone or point |
|
HH |
Holdup Alarm Restore |
Alarm condition eliminated |
Zone or point |
|
HJ |
Holdup Trouble Restore |
Trouble condition eliminated |
Zone or point |
|
HR |
Holdup Restoral |
Alarm/trouble condition has been eliminated |
Zone or point |
|
HS |
Holdup Supervisory |
Unsafe holdup system condition |
Zone or point |
|
HT |
Holdup Trouble |
Zone disabled by fault |
Zone or point |
|
HU |
Holdup Unbypass |
Bypass has been removed |
Zone or point |
|
IA |
Equipment Failure Condition |
A specific, reportable condition is detected on a device |
Point number |
|
IR |
Equipment Fail - Restoral |
The equipment condition has been restored to normal |
Point number |
|
JA |
User Code Tamper |
Too many unsuccessful attempts have been made to enter a user ID |
Area number |
|
JD |
Date Changed |
The date was changed in the transmitter/receiver |
User number |
|
JH |
Holiday Changed |
The transmitter's holiday schedule has been changed |
User number |
|
JK |
Latchkey Alert |
A designated user passcode has not been entered during a scheduled time window |
User number |
|
JL |
Log Threshold |
The transmitter's log memory has reached its threshold level |
Unused |
|
JO |
Log Overflow |
The transmitter's log memory has overflowed |
Unused |
|
JP |
User On Premises |
A designated user passcode has been used to gain access to the premises. |
User number |
|
Data Code |
Short Description |
Long Description |
Address Field |
|
JR |
Schedule Executed |
An automatic scheduled event was executed |
Area number |
|
JS |
Schedule Changed |
An automatic schedule was changed |
User number |
|
JT |
Time Changed |
The time was changed in the transmitter/receiver |
User number |
|
JV |
User Code Changed |
A user's code has been changed |
User number |
|
JX |
User Code Deleted |
A user's code has been removed |
User number |
|
JY |
User Code Added |
A user’s code has been added |
User number |
|
JZ |
User Level Set |
A user’s authority level has been set |
User number |
|
KA |
Heat Alarm |
High temperature detected on premise |
Zone or point |
|
KB |
Heat Bypass |
Zone has been bypassed |
Zone or point |
|
KH |
Heat Alarm Restore |
Alarm condition eliminated |
Zone or point |
|
KJ |
Heat Trouble Restore |
Trouble condition eliminated |
Zone or point |
|
KR |
Heat Restoral |
Alarm/trouble condition has been eliminated |
Zone or point |
|
KS |
Heat Supervisory |
Unsafe heat detection system condition |
Zone or point |
|
KT |
Heat Trouble |
Zone disabled by fault |
Zone or point |
|
KU |
Heat Unbypass |
Bypass has been removed |
Zone or point |
|
LB |
Local Program |
Begin local programming |
Unused |
|
LD |
Local Program Denied |
Access code incorrect |
Unused |
|
LE |
Listen-in Ended |
The listen-in session has been terminated |
Unused |
|
LF |
Listen-in Begin |
The listen-in session with the RECEIVER has begun |
Unused |
|
LR |
Phone Line Restoral |
Phone line restored to service |
Line number |
|
LS |
Local Program Success |
Local programming successful |
Unused |
|
LT |
Phone Line Trouble |
Phone line trouble report |
Line number |
|
LU |
Local Program Fail |
Local programming unsuccessful |
Unused |
|
LX |
Local Programming Ended |
A local programming session has been terminated |
Unused |
|
MA |
Medical Alarm |
Emergency assistance request |
Zone or point |
|
MB |
Medical Bypass |
Zone has been bypassed |
Zone or point |
|
MH |
Medical Alarm Restore |
Alarm condition eliminated |
Zone or point |
|
MI |
Message |
A canned message is being sent |
Message number |
|
MJ |
Medical Trouble Restore |
Trouble condition eliminated |
Zone or point |
|
MR |
Medical Restoral |
Alarm/trouble condition has been eliminated |
Zone or point |
|
MS |
Medical Supervisory |
Unsafe system condition exists |
Zone or point |
|
MT |
Medical Trouble |
Zone disabled by fault |
Zone or point |
|
MU |
Medical Unbypass |
Bypass has been removed |
Zone or point |
|
NA |
No Activity |
There has been no zone activity for a programmed amount of time |
Zone number |
|
NC |
Network Condition |
A communications network has a specific reportable condition |
Network number |
|
NF |
Forced Perimeter Arm |
Some zones/points not ready |
Area number |
|
Data Code |
Short Description |
Long Description |
Address Field |
|
NL |
Perimeter Armed |
An area has been perimeter armed |
Area number |
|
NM |
Perimeter Armed, User Defined |
A user defined area has been perimeter armed |
Area number |
|
NR |
Network Restoral |
A communications network has returned to normal operation |
Network number |
|
NS |
Activity Resumed |
A zone has detected activity after an alert |
Zone number |
|
NT |
Network Failure |
A communications network has failed |
Network number |
|
OA |
Automatic Opening |
System has disarmed automatically |
Area number |
|
OC |
Cancel Report |
Untyped zone cancel |
User number |
|
OG |
Open Area |
System has been partially disarmed |
Area number |
|
OH |
Early to Open from Alarm |
An area in alarm was disarmed before the opening window |
User number |
|
OI |
Fail to Open |
An area has not been armed at the end of the opening window |
Area number |
|
OJ |
Late Open |
An area was disarmed after the opening window |
User number |
|
OK |
Early Open |
An area was disarmed before the opening window |
User number |
|
OL |
Late to Open from Alarm |
An area in alarm was disarmed after the opening window |
User number |
|
OP |
Opening Report |
Account was disarmed |
User number |
|
OQ |
Remote Opening |
The system was disarmed from a remote location |
User number |
|
OR |
Disarm From Alarm |
Account in alarm was reset/disarmed |
User number |
|
OS |
Opening Keyswitch |
Account has been disarmed by keyswitch |
Zone or point |
|
OT |
Late To Close |
System was not armed on time |
User number |
|
OU |
Output State – Trouble |
An output on a peripheral device or NAC is not functioning |
Output number |
|
OV |
Output State – Restore |
An output on a peripheral device or NAC is back to normal operation |
Output number |
|
OZ |
Point Opening |
A point, rather than a full area or account, disarmed |
Zone or point |
|
PA |
Panic Alarm |
Emergency assistance request, manually activated |
Zone or point |
|
PB |
Panic Bypass |
Panic zone has been bypassed |
Zone or point |
|
PH |
Panic Alarm Restore |
Alarm condition eliminated |
Zone or point |
|
PJ |
Panic Trouble Restore |
Trouble condition eliminated |
Zone or point |
|
PR |
Panic Restoral |
Alarm/trouble condition has been eliminated |
Zone or point |
|
PS |
Panic Supervisory |
Unsafe system condition exists |
Zone or point |
|
PT |
Panic Trouble |
Zone disabled by fault |
Zone or point |
|
PU |
Panic Unbypass |
Panic zone bypass has been removed |
Zone or point |
|
QA |
Emergency Alarm |
Emergency assistance request |
Zone or point |
|
QB |
Emergency Bypass |
Zone has been bypassed |
Zone or point |
|
QH |
Emergency Alarm Restore |
Alarm condition has been eliminated |
Zone or point |
|
QJ |
Emergency Trouble Restore |
Trouble condition has been eliminated |
Zone or point |
|
QR |
Emergency Restoral |
Alarm/trouble condition has been eliminated |
Zone or point |
|
Data Code |
Short Description |
Long Description |
Address Field |
|
QS |
Emergency Supervisory |
Unsafe system condition exists |
Zone or point |
|
QT |
Emergency Trouble |
Zone disabled by fault |
Zone or point |
|
QU |
Emergency Unbypass |
Bypass has been removed |
Zone or point |
|
RA |
Remote Programmer Call Failed |
Transmitter failed to communicate with the remote programmer |
Unused |
|
RB |
Remote Program Begin |
Remote programming session initiated |
Unused |
|
RC |
Relay Close |
A relay has energized |
Relay number |
|
RD |
Remote Program Denied |
Access passcode incorrect |
Unused |
|
RN |
Remote Reset |
A TRANSMITTER was reset via a remote programmer |
Unused |
|
RO |
Relay Open |
A relay has de-energized |
Relay number |
|
RP |
Automatic Test |
Automatic communication test report |
Unused |
|
RR |
Power Up |
System lost power, is now restored |
Unused |
|
RS |
Remote Program Success |
Remote programming successful |
Unused |
|
RT |
Data Lost |
Dialer data lost, transmission error |
Line number |
|
RU |
Remote Program Fail |
Remote programming unsuccessful |
Unused |
|
RX |
Manual Test |
Manual communication test report |
User number |
|
RY |
Test Off Normal |
Test signal(s) indicates abnormal condition(s) exist |
Zone or point |
|
SA |
Sprinkler Alarm |
Sprinkler flow condition exists |
Zone or point |
|
SB |
Sprinkler Bypass |
Sprinkler zone has been bypassed |
Zone or point |
|
SC |
Change of State |
An expansion/peripheral device is reporting a new condition or state change |
Condition number |
|
SH |
Sprinkler Alarm Restore |
Alarm condition eliminated |
Zone or point |
|
SJ |
Sprinkler Trouble Restore |
Trouble condition eliminated |
Zone or point |
|
SR |
Sprinkler Restoral |
Alarm/trouble condition has been eliminated |
Zone or point |
|
SS |
Sprinkler Supervisory |
Unsafe sprinkler system condition |
Zone or point |
|
ST |
Sprinkler Trouble |
Zone disabled by fault |
Zone or point |
|
SU |
Sprinkler Unbypass |
Sprinkler zone bypass has been removed |
Zone or point |
|
TA |
Tamper Alarm |
Alarm equipment enclosure opened |
Zone or point |
|
TB |
Tamper Bypass |
Tamper detection has been bypassed |
Zone or point |
|
TC |
All Points Tested |
All point tested |
Unused |
|
TE |
Test End |
Communicator restored to operation |
Unused |
|
TH |
Tamper Alarm Restore |
An Expansion Device’s tamper switch restores to normal from an Alarm state |
Unused |
|
TJ |
Tamper Trouble Restore |
An Expansion Device’s tamper switch restores to normal from a Trouble state |
Unused |
|
TP |
Walk Test Point |
This point was tested during a Walk Test |
Point number |
|
TR |
Tamper Restoral |
Alarm equipment enclosure has been closed |
Zone or point |
|
TS |
Test Start |
Communicator taken out of operation |
Unused |
|
Data Code |
Short Description |
Long Description |
Address Field |
|
TT |
Tamper Trouble |
Equipment enclosure opened in disarmed state |
Zone or point |
|
TU |
Tamper Unbypass |
Tamper detection bypass has been removed |
Zone or point |
|
TW |
Area Watch Start |
Area watch feature has been activated |
Unused |
|
TX |
Test Report |
An unspecified (manual or automatic) communicator test |
Unused |
|
TZ |
Area Watch End |
Area watch feature has been deactivated |
Unused |
|
UA |
Untyped Zone Alarm |
Alarm condition from zone of unknown type |
Zone or point |
|
UB |
Untyped Zone Bypass |
Zone of unknown type has been bypassed |
Zone or point |
|
UG |
Unverified Event – Untyped |
A point assigned to a Cross Point group has gone into alarm but the Cross Point remained normal |
Zone or point |
|
UH |
Untyped Alarm Restore |
Alarm condition eliminated |
Zone or point |
|
UJ |
Untyped Trouble Restore |
Trouble condition eliminated |
Zone or point |
|
UR |
Untyped Zone Restoral |
Alarm/trouble condition eliminated from zone of unknown type |
Zone or point |
|
US |
Untyped Zone Supervisory |
Unsafe condition from zone of unknown type |
Zone or point |
|
UT |
Untyped Zone Trouble |
Trouble condition from zone of unknown type |
Zone or point |
|
UU |
Untyped Zone Unbypass |
Bypass on zone of unknown type has been removed |
Zone or point |
|
UX |
Undefined |
An undefined alarm condition has occurred |
Unused |
|
UY |
Untyped Missing Trouble |
A point or device which was not armed is now logically missing |
Zone or point |
|
UZ |
Untyped Missing Alarm |
A point or device which was armed is now logically missing |
Zone or point |
|
VI |
Printer Paper In |
TRANSMITTER or RECEIVER paper in |
Printer number |
|
VO |
Printer Paper Out |
TRANSMITTER or RECEIVER paper out |
Printer number |
|
VR |
Printer Restore |
TRANSMITTER or RECEIVER trouble restored |
Printer number |
|
VT |
Printer Trouble |
TRANSMITTER or RECEIVER trouble |
Printer number |
|
VX |
Printer Test |
TRANSMITTER or RECEIVER test |
Printer number |
|
VY |
Printer Online |
RECEIVER’S printer is now online |
Unused |
|
VZ |
Printer Offline |
RECEIVER’S printer is now offline |
Unused |
|
WA |
Water Alarm |
Water detected at protected premises |
Zone or point |
|
WB |
Water Bypass |
Water detection has been bypassed |
Zone or point |
|
WH |
Water Alarm Restore |
Water alarm condition eliminated |
Zone or point |
|
WJ |
Water Trouble Restore |
Water trouble condition eliminated |
Zone or point |
|
WR |
Water Restoral |
Water alarm/trouble condition has been eliminated |
Zone or point |
|
WS |
Water Supervisory |
Water unsafe water detection system condition |
Zone or point |
|
WT |
Water Trouble |
Water zone disabled by fault |
Zone or point |
|
WU |
Water Unbypass |
Water detection bypass has been removed |
Zone or point |
|
XA |
Extra Account Report |
CS RECEIVER has received an event from a non-existent account |
Unused |
|
XE |
Extra Point |
Panel has sensed an extra point not specified for this site |
Point number |
|
XF |
Extra RF Point |
Panel has sensed an extra RF point not specified for this site |
Point number |
|
Data Code |
Short Description |
Long Description |
Address Field |
|
XH |
RF Interference Restoral |
A radio device is no longer detecting RF Interference |
Receiver number |
|
XI |
Sensor Reset |
A user has reset a sensor |
Zone or point |
|
XJ |
RF Receiver Tamper Restoral |
A Tamper condition at a premises RF Receiver has been restored |
Receiver number |
|
XL |
Low Received Signal Strength |
The RF signal strength of a reported event is below minimum level |
Receiver number |
|
XM |
Missing Alarm - Cross Point |
Missing Alarm verified by Cross Point in Alarm (or missing) |
Zone or point |
|
XQ |
RF Interference |
A radio device is detecting RF Interference |
Receiver number |
|
XR |
Transmitter Battery Restoral |
Low battery has been corrected |
Zone or point |
|
XS |
RF Receiver Tamper |
A Tamper condition at a premises receiver is detected |
Receiver number |
|
XT |
Transmitter Battery Trouble |
Low battery in wireless transmitter |
Zone or point |
|
XW |
Forced Point |
A point was forced out of the system at arm time |
Zone or point |
|
XX |
Fail to Test |
A specific test from a panel was not received |
Unused |
|
YA |
Bell Fault |
A trouble condition has been detected on a Local Bell, Siren, or Annunciator |
Unused |
|
YB |
Busy Seconds |
Percent of time receiver's line card is on-line |
Line card number |
|
YC |
Communications Fail |
RECEIVER and TRANSMITTER |
Unused |
|
YD |
Receiver Line Card Trouble |
A line card identified by the passed address is in trouble |
Line card number |
|
YE |
Receiver Line Card Restored |
A line card identified by the passed address is restored |
Line card number |
|
YF |
Parameter Checksum Fail |
System data corrupted |
Unused |
|
YG |
Parameter Changed |
A TRANSMITTER’S parameters have been changed |
Unused |
|
YH |
Bell Restored |
A trouble condition has been restored on a Local Bell, Siren, or Annunciator |
Unused |
|
YI |
Overcurrent Trouble |
An Expansion Device has detected an overcurrent condition |
Unused |
|
YJ |
Overcurrent Restore |
An Expansion Device has restored from an overcurrent condition |
Unused |
|
YK |
Communications Restoral |
TRANSMITTER has resumed communication with a RECEIVER |
Unused |
|
YM |
System Battery Missing |
TRANSMITTER/RECEIVER battery is missing |
Unused |
|
YN |
Invalid Report |
TRANSMITTER has sent a packet with invalid data |
Unused |
|
YO |
Unknown Message |
An unknown message was received from automation or the printer |
Unused |
|
YP |
Power Supply Trouble |
TRANSMITTER/RECEIVER has a problem with the power supply |
Unused |
|
YQ |
Power Supply Restored |
TRANSMITTER’S/RECEIVER’S power supply has been restored |
Unused |
|
YR |
System Battery Restoral |
Low battery has been corrected |
Unused |
|
YS |
Communications Trouble |
RECEIVER and TRANSMITTER |
Unused |
|
Data Code |
Short Description |
Long Description |
Address Field |
|
YT |
System Battery Trouble |
Low battery in control/communicator |
Unused |
|
YU |
Diagnostic Error |
An expansion/peripheral device is reporting a diagnostic error |
Condition number |
|
YW |
Watchdog Reset |
The TRANSMITTER created an internal reset |
Unused |
|
YX |
Service Required |
A TRANSMITTER/RECEIVER needs service |
Unused |
|
YY |
Status Report |
This is a header for an account status report transmission |
Unused |
|
YZ |
Service Completed |
Required TRANSMITTER / RECEIVER service completed |
Mfr defined |
|
ZA |
Freeze Alarm |
Low temperature detected at premises |
Zone or point |
|
ZB |
Freeze Bypass |
Low temperature detection has been bypassed |
Zone or point |
|
ZH |
Freeze Alarm Restore |
Alarm condition eliminated |
Zone or point |
|
ZJ |
Freeze Trouble Restore |
Trouble condition eliminated |
Zone or point |
|
ZR |
Freeze Restoral |
Alarm/trouble condition has been eliminated |
Zone or point |
|
ZS |
Freeze Supervisory |
Unsafe freeze detection system condition |
Zone or point |
|
ZT |
Freeze Trouble |
Zone disabled by fault |
Zone or point |
|
ZU |
Freeze Unbypass |
Low temperature detection bypass removed |
Zone or point |