SIA Event Block Data Code Definitions

 

Data Code

Short Description

Long Description

Address Field

AA

Alarm – Panel Substitution

An attempt to substitute an alternate alarm panel for a secure panel has been made

Condition number

AB

Abort

An event message was not sent due to User action

Zone or point

AN

Analog Restoral

An analog fire sensor has been restored to normal operation

Zone or point

AR

AC Restoral

AC power has been restored

Unused

AS

Analog Service

An analog fire sensor needs to be cleaned or calibrated

Zone or point

AT

AC Trouble

AC power has been failed

Unused

BA

Burglary Alarm

Burglary zone has been violated while armed

Zone or point

BB

Burglary Bypass

Burglary zone has been bypassed

Zone or point

BC

Burglary Cancel

Alarm has been cancelled by authorized user

User number

BD

Swinger Trouble

A non-fire zone has been violated after a Swinger Shutdown on the zone

Zone or point

BE

Swinger Trouble Restore

A non-fire zone restores to normal from a Swinger Trouble state

Zone or point

BG

Unverified Event - Burglary

A point assigned to a Cross Point group has gone into alarm but the Cross Point remained normal

Zone or point

BH

Burglary Alarm Restore

Alarm condition eliminated

Zone or point

BJ

Burglary Trouble Restore

Trouble condition eliminated

Zone or point

BM

Burglary Alarm - Cross Point

Burglary alarm w/cross point also in alarm - alarm verified

Zone or point

BR

Burglary Restoral

Alarm/trouble condition has been eliminated

Zone or point

BS

Burglary Supervisory

Unsafe intrusion detection system condition

Zone or point

BT

Burglary Trouble

Burglary zone disabled by fault

Zone or point

BU

Burglary Unbypass

Zone bypass has been removed

Zone or point

BV

Burglary Verified

A burglary alarm has occurred and been verified within programmed conditions. (zone or point not sent)

Area number

BX

Burglary Test

Burglary zone activated during testing

Zone or point

BZ

Missing Supervision

A non-fire Supervisory point has gone missing

Zone or point

CA

Automatic Closing

System armed automatically

Area number

CD

Closing Delinquent

The system has not been armed for a programmed amount of time

Area number

CE

Closing Extend

Extend closing time

User number

CF

Forced Closing

System armed, some zones not ready

User number

CG

Close Area

System has been partially armed

Area number

CI

Fail to Close

An area has not been armed at the end of the closing window

Area number


Data Code

Short Description

Long Description

Address Field

CJ

Late Close

An area was armed after the closing window

User number

CK

Early Close

An area was armed before the closing window

User number

CL

Closing Report

System armed, normal

User number

CM

Missing Alarm Recent Closing

A point has gone missing within 2 minutes of closing

Zone or point

CO

Command Sent

A command has been sent to an expansion/peripheral device

Condition number

CP

Automatic Closing

System armed automatically

User number

CQ

Remote Closing

The system was armed from a remote location

User number

CR

Recent Closing

An alarm occurred within five minutes after the system was closed

User number

CS

Closing Keyswitch

Account has been armed by keyswitch

Zone or point

CT

Late to Open

System was not disarmed on time

Area number

CW

Was Force Armed

Header for a force armed session, forced point msgs may follow

Area number

CX

Custom Function Executed

The panel has executed a preprogrammed set of instructions

Custom    Function number

CZ

Point Closing

A point, as opposed to a whole area or account, has closed

Zone or point

DA

Card Assigned

An access ID has been added to the controller

User number

DB

Card Deleted

An access ID has been deleted from the controller

User number

DC

Access Closed

Access to all users prohibited

Door number

DD

Access Denied

Access denied, unknown code

Door number

DE

Request to Enter

An access point was opened via a Request to Enter device

Door number

DF

Door Forced

Door opened without access request

Door number

DG

Access Granted

Door access granted

Door number

DH

Door Left Open - Restoral

An access point in a Door Left Open state has restored

Door number

DI

Access Denied – Passback

Access denied because credential has not exited area before attempting to re-enter same area

Door number

DJ

Door Forced - Trouble

An access point has been forced open in an unarmed area

Door number

DK

Access Lockout

Access denied, known code

Door number

DL

Door Left Open - Alarm

An open access point when open time expired in an armed area

Door number

DM

Door Left Open - Trouble

An open access point when open time expired in an unarmed area

Door number

DN

Door             Left             Open (non-alarm, non-trouble)

An access point was open when the door cycle time expired

Door number

DO

Access Open

Access to authorized users allowed

Door number

DP

Access            Denied            Unauthorized Time

An access request was denied because the request is occurring outside the user’s authorized time window(s)

Door number

DQ

Access Denied Unauthorized Arming State

An access request was denied because the user was not authorized in this area when the area was armed

Door number

DR

Door Restoral

Access alarm/trouble condition eliminated

Door number

DS

Door Station

Identifies door for next report

Door number


Data Code

Short Description

Long Description

Address Field

DT

Access Trouble

Access system trouble

Unused

DU

Dealer ID

Dealer ID number

Dealer ID

DV

Access Denied Unauthorized Entry Level

An access request was denied because the user is not authorized in this area

Door number

DW

Access            Denied            Interlock

An access request was denied because the doors associated Interlock point is open

Door number

DX

Request to Exit

An access point was opened via a Request to Exit device

Door number

DY

Door Locked

The door’s lock has been engaged

Door number

DZ

Access            Denied            Door Secured

An access request was denied because the door has been placed in an Access Closed state

Door number

EA

Exit Alarm

An exit zone remained violated at the end of the exit delay period

Zone or point

EE

Exit Error

An exit zone remained violated at the end of the exit delay period

User number

EJ

Expansion Tamper Restore

Expansion device tamper restoral

Expansion device number

EM

Expansion Device Missing

Expansion device missing

Expansion device number

EN

Expansion Missing Restore

Expansion device communications re-established

Expansion device number

ER

Expansion Restoral

Expansion device trouble eliminated

Expander number

ES

Expansion Device Tamper

Expansion device enclosure tamper

Expansion device number

ET

Expansion Trouble

Expansion device trouble

Expander number

EX

External Device Condition

A specific reportable condition is detected on an external device

Device number

EZ

Missing Alarm - Exit Error

A point remained missing at the end of the exit delay period

Point number

FA

Fire Alarm

Fire condition detected

Zone or point

FB

Fire Bypass

Zone has been bypassed

Zone or point

FC

Fire Cancel

A Fire Alarm has been cancelled by an authorized person

Zone or point

FG

Unverified Event – Fire

A point assigned to a Cross Point group has gone into alarm but the Cross Point remained normal

Zone or point

FH

Fire Alarm Restore

Alarm condition eliminated

Zone or point

FI

Fire Test Begin

The transmitter area's fire test has begun

Area number

FJ

Fire Trouble Restore

Trouble condition eliminated

Zone or point

FK

Fire Test End

The transmitter area's fire test has ended

Area number

FL

Fire Alarm Silenced

The fire panel’s sounder was silenced by command

Zone or point

FM

Fire Alarm - Cross Point

Fire Alarm with Cross Point also in alarm verifying the Fire Alarm

Point number

FQ

Fire     Supervisory    Trouble Restore

A fire supervisory zone that was in trouble condition has now restored to normal

Zone or point

FR

Fire Restoral

Alarm/trouble condition has been eliminated

Zone or point


Data Code

Short Description

Long Description

Address Field

FS

Fire Supervisory

Unsafe fire detection system condition

Zone or point

FT

Fire Trouble

Zone disabled by fault

Zone or point

FU

Fire Unbypass

Bypass has been removed

Zone or point

FV

Fire Supervision Restore

A fire supervision zone that was in alarm has restored to normal

Zone or point

FW

Fire Supervisory Trouble

A fire supervisory zone is now in a trouble condition

Zone or point

FX

Fire Test

Fire zone activated during test

Zone or point

FY

Missing Fire Trouble

A fire point is now logically missing

Zone or point

FZ

Missing Fire Supervision

A Fire Supervisory point has gone missing

Zone or point

GA

Gas Alarm

Gas alarm condition detected

Zone or point

GB

Gas Bypass

Zone has been bypassed

Zone or point

GH

Gas Alarm Restore

Alarm condition eliminated

Zone or point

GJ

Gas Trouble Restore

Trouble condition eliminated

Zone or point

GR

Gas Restoral

Alarm/trouble condition has been eliminated

Zone or point

GS

Gas Supervisory

Unsafe gas detection system condition

Zone or point

GT

Gas Trouble

Zone disabled by fault

Zone or point

GU

Gas Unbypass

Bypass has been removed

Zone or point

GX

Gas Test

Zone activated during test

Zone or point

HA

Holdup Alarm

Silent alarm, user under duress

Zone or point

HB

Holdup Bypass

Zone has been bypassed

Zone or point

HH

Holdup Alarm Restore

Alarm condition eliminated

Zone or point

HJ

Holdup Trouble Restore

Trouble condition eliminated

Zone or point

HR

Holdup Restoral

Alarm/trouble condition has been eliminated

Zone or point

HS

Holdup Supervisory

Unsafe holdup system condition

Zone or point

HT

Holdup Trouble

Zone disabled by fault

Zone or point

HU

Holdup Unbypass

Bypass has been removed

Zone or point

IA

Equipment Failure Condition

A specific, reportable condition is detected on a device

Point number

IR

Equipment Fail - Restoral

The equipment condition has been restored to normal

Point number

JA

User Code Tamper

Too many unsuccessful attempts have been made to enter a user ID

Area number

JD

Date Changed

The date was changed in the transmitter/receiver

User number

JH

Holiday Changed

The transmitter's holiday schedule has been changed

User number

JK

Latchkey Alert

A designated user passcode has not been entered during a scheduled time window

User number

JL

Log Threshold

The transmitter's log memory has reached its threshold level

Unused

JO

Log Overflow

The transmitter's log memory has overflowed

Unused

JP

User On Premises

A designated user passcode has been used to gain access to the premises.

User number


Data Code

Short Description

Long Description

Address Field

JR

Schedule Executed

An automatic scheduled event was executed

Area number

JS

Schedule Changed

An automatic schedule was changed

User number

JT

Time Changed

The time was changed in the transmitter/receiver

User number

JV

User Code Changed

A user's code has been changed

User number

JX

User Code Deleted

A user's code has been removed

User number

JY

User Code Added

A user’s code has been added

User number

JZ

User Level Set

A user’s authority level has been set

User number

KA

Heat Alarm

High temperature detected on premise

Zone or point

KB

Heat Bypass

Zone has been bypassed

Zone or point

KH

Heat Alarm Restore

Alarm condition eliminated

Zone or point

KJ

Heat Trouble Restore

Trouble condition eliminated

Zone or point

KR

Heat Restoral

Alarm/trouble condition has been eliminated

Zone or point

KS

Heat Supervisory

Unsafe heat detection system condition

Zone or point

KT

Heat Trouble

Zone disabled by fault

Zone or point

KU

Heat Unbypass

Bypass has been removed

Zone or point

LB

Local Program

Begin local programming

Unused

LD

Local Program Denied

Access code incorrect

Unused

LE

Listen-in Ended

The listen-in session has been terminated

Unused

LF

Listen-in Begin

The listen-in session with the RECEIVER has begun

Unused

LR

Phone Line Restoral

Phone line restored to service

Line number

LS

Local Program Success

Local programming successful

Unused

LT

Phone Line Trouble

Phone line trouble report

Line number

LU

Local Program Fail

Local programming unsuccessful

Unused

LX

Local Programming Ended

A local programming session has been terminated

Unused

MA

Medical Alarm

Emergency assistance request

Zone or point

MB

Medical Bypass

Zone has been bypassed

Zone or point

MH

Medical Alarm Restore

Alarm condition eliminated

Zone or point

MI

Message

A canned message is being sent

Message number

MJ

Medical Trouble Restore

Trouble condition eliminated

Zone or point

MR

Medical Restoral

Alarm/trouble condition has been eliminated

Zone or point

MS

Medical Supervisory

Unsafe system condition exists

Zone or point

MT

Medical Trouble

Zone disabled by fault

Zone or point

MU

Medical Unbypass

Bypass has been removed

Zone or point

NA

No Activity

There has been no zone activity for a programmed amount of time

Zone number

NC

Network Condition

A communications network has a specific reportable condition

Network number

NF

Forced Perimeter Arm

Some zones/points not ready

Area number


Data Code

Short Description

Long Description

Address Field

NL

Perimeter Armed

An area has been perimeter armed

Area number

NM

Perimeter     Armed,      User Defined

A user defined area has been perimeter armed

Area number

NR

Network Restoral

A communications network has returned to normal operation

Network number

NS

Activity Resumed

A zone has detected activity after an alert

Zone number

NT

Network Failure

A communications network has failed

Network number

OA

Automatic Opening

System has disarmed automatically

Area number

OC

Cancel Report

Untyped zone cancel

User number

OG

Open Area

System has been partially disarmed

Area number

OH

Early to Open from Alarm

An area in alarm was disarmed before the opening window

User number

OI

Fail to Open

An area has not been armed at the end of the opening window

Area number

OJ

Late Open

An area was disarmed after the opening window

User number

OK

Early Open

An area was disarmed before the opening window

User number

OL

Late to Open from Alarm

An area in alarm was disarmed after the opening window

User number

OP

Opening Report

Account was disarmed

User number

OQ

Remote Opening

The system was disarmed from a remote location

User number

OR

Disarm From Alarm

Account in alarm was reset/disarmed

User number

OS

Opening Keyswitch

Account has been disarmed by keyswitch

Zone or point

OT

Late To Close

System was not armed on time

User number

OU

Output State – Trouble

An output on a peripheral device or NAC is not functioning

Output number

OV

Output State – Restore

An output on a peripheral device or NAC is back to normal operation

Output number

OZ

Point Opening

A point, rather than a full area or account, disarmed

Zone or point

PA

Panic Alarm

Emergency assistance request, manually activated

Zone or point

PB

Panic Bypass

Panic zone has been bypassed

Zone or point

PH

Panic Alarm Restore

Alarm condition eliminated

Zone or point

PJ

Panic Trouble Restore

Trouble condition eliminated

Zone or point

PR

Panic Restoral

Alarm/trouble condition has been eliminated

Zone or point

PS

Panic Supervisory

Unsafe system condition exists

Zone or point

PT

Panic Trouble

Zone disabled by fault

Zone or point

PU

Panic Unbypass

Panic zone bypass has been removed

Zone or point

QA

Emergency Alarm

Emergency assistance request

Zone or point

QB

Emergency Bypass

Zone has been bypassed

Zone or point

QH

Emergency Alarm Restore

Alarm condition has been eliminated

Zone or point

QJ

Emergency Trouble Restore

Trouble condition has been eliminated

Zone or point

QR

Emergency Restoral

Alarm/trouble condition has been eliminated

Zone or point


Data Code

Short Description

Long Description

Address Field

QS

Emergency Supervisory

Unsafe system condition exists

Zone or point

QT

Emergency Trouble

Zone disabled by fault

Zone or point

QU

Emergency Unbypass

Bypass has been removed

Zone or point

RA

Remote Programmer Call Failed

Transmitter failed to communicate with the remote programmer

Unused

RB

Remote Program Begin

Remote programming session initiated

Unused

RC

Relay Close

A relay has energized

Relay number

RD

Remote Program Denied

Access passcode incorrect

Unused

RN

Remote Reset

A TRANSMITTER was reset via a remote programmer

Unused

RO

Relay Open

A relay has de-energized

Relay number

RP

Automatic Test

Automatic communication test report

Unused

RR

Power Up

System lost power, is now restored

Unused

RS

Remote Program Success

Remote programming successful

Unused

RT

Data Lost

Dialer data lost, transmission error

Line number

RU

Remote Program Fail

Remote programming unsuccessful

Unused

RX

Manual Test

Manual communication test report

User number

RY

Test Off Normal

Test signal(s) indicates abnormal condition(s) exist

Zone or point

SA

Sprinkler Alarm

Sprinkler flow condition exists

Zone or point

SB

Sprinkler Bypass

Sprinkler zone has been bypassed

Zone or point

SC

Change of State

An expansion/peripheral device is reporting a new condition or state change

Condition number

SH

Sprinkler Alarm Restore

Alarm condition eliminated

Zone or point

SJ

Sprinkler Trouble Restore

Trouble condition eliminated

Zone or point

SR

Sprinkler Restoral

Alarm/trouble condition has been eliminated

Zone or point

SS

Sprinkler Supervisory

Unsafe sprinkler system condition

Zone or point

ST

Sprinkler Trouble

Zone disabled by fault

Zone or point

SU

Sprinkler Unbypass

Sprinkler zone bypass has been removed

Zone or point

TA

Tamper Alarm

Alarm equipment enclosure opened

Zone or point

TB

Tamper Bypass

Tamper detection has been bypassed

Zone or point

TC

All Points Tested

All point tested

Unused

TE

Test End

Communicator restored to operation

Unused

TH

Tamper Alarm Restore

An Expansion Device’s tamper switch restores to normal from an Alarm state

Unused

TJ

Tamper Trouble Restore

An Expansion Device’s tamper switch restores to normal from a Trouble state

Unused

TP

Walk Test Point

This point was tested during a Walk Test

Point number

TR

Tamper Restoral

Alarm equipment enclosure has been closed

Zone or point

TS

Test Start

Communicator taken out of operation

Unused


Data Code

Short Description

Long Description

Address Field

TT

Tamper Trouble

Equipment enclosure opened in disarmed state

Zone or point

TU

Tamper Unbypass

Tamper detection bypass has been removed

Zone or point

TW

Area Watch Start

Area watch feature has been activated

Unused

TX

Test Report

An unspecified (manual or automatic) communicator test

Unused

TZ

Area Watch End

Area watch feature has been deactivated

Unused

UA

Untyped Zone Alarm

Alarm condition from zone of unknown type

Zone or point

UB

Untyped Zone Bypass

Zone of unknown type has been bypassed

Zone or point

UG

Unverified Event – Untyped

A point assigned to a Cross Point group has gone into alarm but the Cross Point remained normal

Zone or point

UH

Untyped Alarm Restore

Alarm condition eliminated

Zone or point

UJ

Untyped Trouble Restore

Trouble condition eliminated

Zone or point

UR

Untyped Zone Restoral

Alarm/trouble condition eliminated from zone of unknown type

Zone or point

US

Untyped Zone Supervisory

Unsafe condition from zone of unknown type

Zone or point

UT

Untyped Zone Trouble

Trouble condition from zone of unknown type

Zone or point

UU

Untyped Zone Unbypass

Bypass on zone of unknown type has been removed

Zone or point

UX

Undefined

An undefined alarm condition has occurred

Unused

UY

Untyped Missing Trouble

A point or device which was not armed is now logically missing

Zone or point

UZ

Untyped Missing Alarm

A point or device which was armed is now logically missing

Zone or point

VI

Printer Paper In

TRANSMITTER or RECEIVER paper in

Printer number

VO

Printer Paper Out

TRANSMITTER or RECEIVER paper out

Printer number

VR

Printer Restore

TRANSMITTER or RECEIVER trouble restored

Printer number

VT

Printer Trouble

TRANSMITTER or RECEIVER trouble

Printer number

VX

Printer Test

TRANSMITTER or RECEIVER test

Printer number

VY

Printer Online

RECEIVER’S printer is now online

Unused

VZ

Printer Offline

RECEIVER’S printer is now offline

Unused

WA

Water Alarm

Water detected at protected premises

Zone or point

WB

Water Bypass

Water detection has been bypassed

Zone or point

WH

Water Alarm Restore

Water alarm condition eliminated

Zone or point

WJ

Water Trouble Restore

Water trouble condition eliminated

Zone or point

WR

Water Restoral

Water alarm/trouble condition has been eliminated

Zone or point

WS

Water Supervisory

Water unsafe water detection system condition

Zone or point

WT

Water Trouble

Water zone disabled by fault

Zone or point

WU

Water Unbypass

Water detection bypass has been removed

Zone or point

XA

Extra Account Report

CS RECEIVER has received an event from a non-existent account

Unused

XE

Extra Point

Panel has sensed an extra point not specified for this site

Point number

XF

Extra RF Point

Panel has sensed an extra RF point not specified for this site

Point number


Data Code

Short Description

Long Description

Address Field

XH

RF Interference Restoral

A radio device is no longer detecting RF Interference

Receiver number

XI

Sensor Reset

A user has reset a sensor

Zone or point

XJ

RF        Receiver        Tamper Restoral

A Tamper condition at a premises RF Receiver has been restored

Receiver number

XL

Low        Received        Signal Strength

The RF signal strength of a reported event is below minimum level

Receiver number

XM

Missing Alarm - Cross Point

Missing Alarm verified by Cross Point in Alarm (or missing)

Zone or point

XQ

RF Interference

A radio device is detecting RF Interference

Receiver number

XR

Transmitter Battery Restoral

Low battery has been corrected

Zone or point

XS

RF Receiver Tamper

A Tamper condition at a premises receiver is detected

Receiver number

XT

Transmitter Battery Trouble

Low battery in wireless transmitter

Zone or point

XW

Forced Point

A point was forced out of the system at arm time

Zone or point

XX

Fail to Test

A specific test from a panel was not received

Unused

YA

Bell Fault

A trouble condition has been detected on a Local Bell, Siren, or Annunciator

Unused

YB

Busy Seconds

Percent of time receiver's line card is on-line

Line card number

YC

Communications Fail

RECEIVER and TRANSMITTER

Unused

YD

Receiver Line Card Trouble

A line card identified by the passed address is in trouble

Line card number

YE

Receiver         Line         Card Restored

A line card identified by the passed address is restored

Line card number

YF

Parameter Checksum Fail

System data corrupted

Unused

YG

Parameter Changed

A TRANSMITTER’S parameters have been changed

Unused

YH

Bell Restored

A trouble condition has been restored on a Local Bell, Siren, or Annunciator

Unused

YI

Overcurrent Trouble

An Expansion Device has detected an overcurrent condition

Unused

YJ

Overcurrent Restore

An Expansion Device has restored from an overcurrent condition

Unused

YK

Communications Restoral

TRANSMITTER      has     resumed     communication    with     RECEIVER

Unused

YM

System Battery Missing

TRANSMITTER/RECEIVER battery is missing

Unused

YN

Invalid Report

TRANSMITTER has sent a packet with invalid data

Unused

YO

Unknown Message

An unknown message was received from automation or the printer

Unused

YP

Power Supply Trouble

TRANSMITTER/RECEIVER has a problem with the power supply

Unused

YQ

Power Supply Restored

TRANSMITTER’S/RECEIVER’S      power    supply    has    been restored

Unused

YR

System Battery Restoral

Low battery has been corrected

Unused

YS

Communications Trouble

RECEIVER and TRANSMITTER

Unused


Data Code

Short Description

Long Description

Address Field

YT

System Battery Trouble

Low battery in control/communicator

Unused

YU

Diagnostic Error

An expansion/peripheral device is reporting a diagnostic error

Condition number

YW

Watchdog Reset

The TRANSMITTER created an internal reset

Unused

YX

Service Required

A TRANSMITTER/RECEIVER needs service

Unused

YY

Status Report

This is a header for an account status report transmission

Unused

YZ

Service Completed

Required TRANSMITTER / RECEIVER service completed

Mfr defined

ZA

Freeze Alarm

Low temperature detected at premises

Zone or point

ZB

Freeze Bypass

Low temperature detection has been bypassed

Zone or point

ZH

Freeze Alarm Restore

Alarm condition eliminated

Zone or point

ZJ

Freeze Trouble Restore

Trouble condition eliminated

Zone or point

ZR

Freeze Restoral

Alarm/trouble condition has been eliminated

Zone or point

ZS

Freeze Supervisory

Unsafe freeze detection system condition

Zone or point

ZT

Freeze Trouble

Zone disabled by fault

Zone or point

ZU

Freeze Unbypass

Low temperature detection bypass removed

Zone or point